POWER SUPPLY
Voltage supply:8-36V DC
Consumption:0.5-0.1A depend on supply voltage
Allowed supply voltage drop-out:50ms from min. 10V,return to min. 8V (valid for InteliLite of hardware version 3.2 and higher)
Battery voltage measurement tolerance:2 % at 24V
Hint: For the supply voltage less than 7V the backlight of the display is switched off.
OPERATING CONDITIONS
Operating temperature IL-CU:-20 to +70°C
Operating temperature IL-CU-LT#:-30 to +70°C
Storage temperature:-30 to +80°C
Protection front panel:IP65
Humidity:95% without condensation
STANDARD CONFORMITY
Low Voltage Directive:EN 61010-1:95 +A1:97
Electromagnetic Compatibility:EN 50081-1:94,EN 50081-2:96,EN 50082-1:99,EN 50082-2:97
Vibration:5 - 25 Hz, ±1.6mm, 25 - 100 Hz, a = 4 g
Shocks:a = 200 m/s²
LOW TEMPERATURE MODIFICATION
LCD display limits controller operating temperature range to –20 °C to + 70 °C even if the other electronic components work in wider temperature range.
Internal preheating foil is mounted in InteliLite LT to extend display operational temperature range.
Preheating starts at temperature below 5 °C and preheating power depends on temperature and power supply voltage.
TECHNICAL DATA
Operating temperature:-20°C to +70°C(IL-CU Standard); -30°C to +70°C(Order code:IL-CU-LT)
Storage temperature:-30°C to +80°C(IL-CU Standard); -30°C to +80°C(Order code:IL-CU-LT)
Preheating foil increases controller current consumption
No preheating:360mA(12VDC);230mA(24VDC);100mA(36VDC)
Preheating at ambient temperature(0°C):+50mA(12VDC);+25mA(24VDC);+20mA(36VDC)
Preheating at ambient temperature(-15°C):+180mA(12VDC);+85mA(24VDC);+150mA(36VDC)
Preheating at ambient temperature(-30°C):+20mA(12VDC);+65mA(24VDC);+100mA(36VDC)
InteliLite LT works immediately after switch on at -30°C and display becomes visible after a few minutes.
Short-term voltage drops (e.g. during the engine cranking) do not affect the operation at all.
DIMENSIONS AND WEIGHT
Dimensions:180x120x55mm
Weight:800g
MAINS AND GENERATOR
Nominal frequency:50-60Hz
Frequency measurement tolerance:0.1Hz
CURRENT INPUTS
Nominal input current (from CT):5 A
Load (CT output impedance):< 0.1 Ω
CT input burden:< 0.2 VA per phase (In=5A)
Max. measured current from CT:10 A
Current measurement tolerance:2% from the Nominal current
Max. peak current from CT:150 A / 1s
Max. continuous current:12 A
VOLTAGE INPUTS
Measuring voltage:231VAC phase to neutral;400VAC phase to phase
Maximal measured voltage:290VAC phase to neutral
Input resistance:0.6 MΩ phase to phase;0.3 MΩ phase to neutral
Voltage measurement tolerance:2 % from the Nominal voltage
Overvoltage class:III (EN61010)
BINARY INPUTS
Number of inputs:7
Input resistance:4.7 kΩ
Input range:0-36 VDC
Switching voltage level for close contact indication:0-2 V
Max voltage level for open contact indication:8-36 V
CONTACT RELAY OUTPUTS
Number of outputs:2
Electric life cycle:min 100.000 switching cycles
Maximum current:12 A DC resistive load;4 A DC inductive load
Maximum switching voltage:36 VDC
Minimum load:24 V / 0.1 A
Insulation voltage:500 Veff
BINARY OPEN COLLECTOR OUTPUTS
Number of outputs:5
Maximum current:0.5 A
Maximum switching voltage:36 VDC
ANALOG INPUTS
Not electrically separated
Resolution:10 bits
Sensor resistance range:0 Ω-2.4 kΩ
Resistance measurement tolerance: 4 % ± 2 Ω out of measured value
SPEED PICK-UP INPUT
Type of sensor:magnetic pick-up (connection by shielded cable is recommended)
Minimum input voltage:2 Vpk-pk (from 4 Hz to 4 kHz)
Maximum input voltage:50 Veff
Minimum measured frequency:4 Hz
Maximum measured frequency:10 kHz (min. input voltage 6Vpk-pk)
Frequency measurement tolerance:1.5 %
*CAN BUS INTERFACE
Galvanically separated
Maximal CAN bus length:200m
Speed:250kBd
Nominal impedance:120Ω
Cable type:twisted pair (shielded)
Following dynamic cable parameters are important especially for maximal 200meters CAN bus length and 32 iS-COM units connected:
Nominal Velocity of Propagation:min. 75% (max. 4.4 ns/m)
Wire crosscut:min.0.25 mm²
Maximal attenuation (at 1 MHz):2 dB / 100m