Model NO. |
EA06 |
Sensing Input |
Terminal 1,2 3,4 5,6 Can be connected to Y or △ 220~480 VAC single phase / three phase 50/60 Hz |
Power Input |
50~280 VAC (1,2) 50/60 Hz |
Output |
Voltage 63 VDC @ 220 VAC Input Current Continuous 6A Max. Intermittent 7A for 10 sec. |
Voltage Regulation |
< ±1% (with 4% engine governing) |
Voltage Build-up |
Residual Voltage above 5 VAC 25 Hz |
External Volts Adjustment |
100 K Ohm 1/2 watt ±5% |
Unit Power Dissipation |
Max. 5 watt |
EMI Suppression |
Internal Electromagnetic Interference Filtering |
Under Frequency Protection |
Adjustable range 42~62 Hz |
Excitation Winding Resistance |
DC Resistance 10~100 Ohm |
Over Excitation Protection |
25~55 VDC @ 0.1~20 sec. |
Environment |
Operating Temperature : -40~65 °C Storage Temperature : -40~80 °C Relative Humidity : Maximum 95% Vibration : 1.5G @ 5~30 Hz / 5.0G @ 30~500 Hz |
AVR Controls Function |
VOLTS : Voltage Adjustment STAB : Stability Adjustment U/F : Under Frequency Protection AMP : Over Excitation Setting |
Dimensions |
150.0 (L) x 114.7 (W) x 35.2 (H) mm |
Weight |
520g ±2% |